MM6010

MM6010
AC Input
Isolated
Plug-In
Mighty Module
Transmitter

$440.00

The following information must be entered to complete your order:
See "Specifications" below for Input and Output range limits.

Power:

Input:
Zero Scale
Full Scale
Units
Output: Zero Scale
Full Scale
Units

Quantity:

 

Don't Forget Your Accessories
DMP008 8-Pin Socket for Panel or DIN-Rail Mounting $20.00
Quantity:
Specifications
CLP1 Hold Down Assembly $20.00
Quantity:
Specifications
HKB-HK2D-8 Explosion Proof Housing With DMP008 Installed $325.00
Quantity:
Specifications
DR1 DIN-Rail, 35mm Symmetrical, 39 inches (1 meter) $25.00
Quantity:
Specifications
TRK48 PVC Snap-Track, 4 ft, for MP011 $30.00
Quantity:
Specifications
 
  • Features
  • Description
  • Specifications
  • Dimensions
  • Connections
  • Provides DC Output Proportional to AC Input Voltage or Current
  • Fully Isolated Output
  • 50 mV or 1 mA Minimum Input Span
  • Unlimited Choice of Input / Output Ranges (Within Specified Range Limits)
  • Choice of Power Options
  • 10 Year Warranty

The MM6010 provides a DC output voltage or current proportional to an AC input signal. It is useful in measuring AC voltages or currents and converting them to DC levels for driving controllers, recorders, meters, or other instruments.
 
It utilizes a precision rectifier system to provide accurate and stable rectification of the
AC input signal. The module provides an output signal proportional to the average level of the input signal. It is calibrated assuming a sinusoidal input signal will be applied. Other calibrations are available.

The MM6010 utilizes a feedback VCO to develop a pulse train with a duty cycle proportional to the input signal amplitude. This pulse train is coupled through a pulse transformer to the output circuitry, where the duty cycle data is converted to a proportional DC level in the input level circuit.

All Wilkerson Products are designed with RFI filters and lightning protection to reduce susceptibility to electrical noise and damage by lightning.

TYPICAL APPLICATIONS

Monitoring power line or power supply voltages and currents. Measuring the output of self-generating process sensors or transducers which generate AC current and measuring current consumption of electrical devices such as motors, pumps or heaters.

INPUT RANGE
Voltage select any range from 0 to 250 V max
(min span 50 mV)
Current select any range from 0 to 1 A rms max**
(min span 1 mA, internal shunt)

INPUT FREQUENCY
40 Hz to 1 kHz sine wave

INPUT IMPEDANCE
Voltage
200 kilohms
Current

Input Value Input Shunt Value
1 mA
10 mA
20 mA
4/20 mA
100 mA
1 A
5 A
100 Ohm
10 Ohm
5 Ohm
61.9 Ohm
1 Ohm
0.1 Ohm
0.01 Ohm

OUTPUT RANGE
Voltage
select any range from - 10 V to +15 V, 10 mA max load
(min span 0.2 V)
Current
select any range from 0 to 50 mA max, > 24 V compliance
(1200 ohms max at 20 mA)

RESPONSE TIME
1 sec typical

ACCURACY
±0.5% of span

LINEARITY
±0.5% of span

COMMON MODE REJECTION
120 dB, DC to 60 Hz

ISOLATION
Output / Input >500 megohms
Breakdown Voltage >1000 VAC rms
Breakdown, Power / Circuitry >1500 VAC rms

OUTPUT RIPPLE
(Peak-to-Peak) ±0.05% of span

OPERATING TEMPERATURE
14°F to 140°F/-10°C to 60°C

TEMPERATURE STABILITY
±0.02% of span/°C

POWER
115 VAC ±10%, 50/60 Hz (2.5 W max)
230 VAC ±10%, 50/60 Hz (2.5 W max)
(DC Power Option)
24 VDC (limits 21-32 VDC)
12 VDC (limits 10-16 VDC)

Isolation, DC power supply to input common: 10 megohms

Mighty Module Dimension Drawing

PIN 1
PIN 2
PIN 3
PIN 4
PIN 5
PIN 6
PIN 7
PIN 8
Power Supply +
No Connection
Power Supply -
No Connection
Input Signal
Input Common
Output +
Output -
Specifications    Manual

Solutions Provider for Signal Conditioning and
Process Control Instrumentation