WILKERSON INSTRUMENT CO., INC.

MM4410 DC Input Plug-In Mighty Module
Multiplier Transmitter Y=(A*B)

Wici Logo
Home Button Wilkerson Instrument Co.    800-234-1343 Wilkerson Instrument Co Blog PageWilkerson Instrument Co LinkedIn PageShopping Cart

MM4410

MM4410
DC Input
Plug-In
Mighty Module
Multiplier Transmitter
Y=(A*B)

$490.00

The following information must be entered to complete your order:
See "Specifications" below for Input and Output range limits.

Power:

Input:
Zero Scale
Full Scale
Units
Output: Zero Scale
Full Scale
Units
  Isolation

Quantity:

 

Don't Forget Your Accessories
DMP008 8-Pin Socket for Panel or DIN-Rail Mounting $20.00
Quantity:
Specifications
CLP1 Hold Down Assembly $20.00
Quantity:
Specifications
HKB-HK2D-8 Explosion Proof Housing With DMP008 Installed $325.00
Quantity:
Specifications
DR1 DIN-Rail, 35mm Symmetrical, 39 inches (1 meter) $25.00
Quantity:
Specifications
TRK48 PVC Snap-Track, 4 ft, for MP011 $30.00
Quantity:
Specifications
 
  • Features
  • Description
  • Specifications
  • Dimensions
  • Connections
  • Provides DC Output Proportional to the Product of Two DC Inputs
  • Fully Isolated Output Available
  • 1 V or 1 mA Minimum Input Span
  • Unlimited Choice of Input/ Output Ranges (Within specified range limits)
  • Choice of Power Options
  • 10 Year Warranty

The MM4410 provides a DC output voltage or current proportional to the product of two DC inputs. Typical input ranges are 4/20 mA, 10/50 mA, 0-1 V, 0-5 V, and 0-10 VDC. Other ranges are available down to minimum spans of 1 V or 1 mA DC. Standard calibration provides the output at full scale (100%) when both inputs are at full scale (100%). Other calibrations are available.

All Wilkerson products are designed with RFI filters and lightning protection to reduce susceptibility to electrical noise and damage by lightning.

TYPICAL APPLICATIONS

Calculating power (current x voltage), mass flow (flow rate x density), etc.

INPUT RANGE
Voltage select any range between ±250 V
(min span 1 V)
Typical inputs: 0-1 V, 0-5 V, 0-10 V
Current select any range between ±100 mA max
(min span 1 mA)
Typical inputs: 4/20 mA or 10/50 mA

INPUT IMPEDANCE
Voltage 100 kilohms
Current 1.25 V drop typical
others available

OUTPUT RANGE
Voltage select any range from -10 V to +15V
10 mA max load (min span 0.2 V)
Current select any range from 0 to 50 mA max
>24 V compliance (1200 ohms max at 20 mA)
18 V compliance for ISO option if full scale output >20 mA

RESPONSE TIME
(Range Dependent) < 150 ms

ACCURACY
± 0.25% of span

ISOLATION (Optional)
Output / Input >500 megohms
Breakdown Voltage >1000 VAC rms
Breakdown, Power / Circuitry >1500 VAC rm

OUTPUT RIPPLE
(Peak-to-Peak) <0.1% of span

OPERATING TEMPERATURE
14°F to 140°F/–10°C to 60°C

TEMPERATURE STABILITY
±0.02% of span/°C max

POWER
115 VAC ±10%, 50/60 Hz (2.5 W max)
230 VAC ±10%, 50/60 Hz (2.5 W max)
(DC Power Option)
24 VDC (limits 21-32 VDC)
12 VDC (limits 10-16 VDC)

Isolation, DC power supply to input common: 10 megohms

Mighty Module Dimension Drawing

PIN 1
PIN 2
PIN 3
PIN 4
PIN 5
PIN 6
PIN 7
PIN 8
AC L1 or DC +
No Connection
AC L2 or DC -
Input A +
Input B +
Input Common
Output +
Output -
Specifications    Manual

Solutions Provider for Signal Conditioning and
Process Control Instrumentation