WILKERSON INSTRUMENT CO., INC.

MM4130 Thermocouple Input Non-Linearized
Plug-In Mighty Module Transmitter

Wici Logo
Home Button Wilkerson Instrument Co.    800-234-1343 Wilkerson Instrument Co Blog PageWilkerson Instrument Co LinkedIn PageShopping Cart

MM4130

MM4130
Thermocouple Input
Non-Linearized
Plug-In
Mighty Module
Transmitter

$470.00

The following information must be entered to complete your order:
See "Specifications" below for Input and Output range limits.

Power:

Input:
Zero Scale
Full Scale
Units
  Thermocouple Type
Output: Zero Scale
Full Scale
Units

Quantity:

 

Don't Forget Your Accessories
DMP008 8-Pin Socket for Panel or DIN-Rail Mounting $20.00
Quantity:
Specifications
CLP1 Hold Down Assembly $20.00
Quantity:
Specifications
HKB-HK2D-8 Explosion Proof Housing With DMP008 Installed $325.00
Quantity:
Specifications
DR1 DIN-Rail, 35mm Symmetrical, 39 inches (1 meter) $25.00
Quantity:
Specifications
TRK48 PVC Snap-Track, 4 ft, for MP011 $30.00
Quantity:
Specifications
 
  • Features
  • Description
  • Specifications
  • Dimensions
  • Connections
  • Provides a Fully Isolated DC Output Proportional to any Thermocouple Input
  • Analog and Digital Linearization Options Available
  • Cold Junction Compensated
  • 5 mV Minimum Input Span
  • Unlimited Choice of Input / Output Ranges (Within specified range limits)
  • Upscale Burnout Protection (Downscale Available)
  • Choice of Power Options
  • 10 Year Warranty

The MM4130 provides a DC output voltage or current, fully isolated from input, line power and ground, proportional to a thermocouple input signal. It is useful in measuring temperatures with any type of thermocouple. Cold junction compensation is provided by a solid state temperature sensor embedded in the thermocouple terminal strip.

All Wilkerson products are designed with RFI filters and lightning protection to reduce susceptibility to electrical noise and damage by lightning.

The module utilizes a feedback VCO to develop a pulse train with a duty cycle proportional to the input signal amplitude. This pulse train is coupled through an isolator where the duty cycle is converted to a proportional DC level in the output circuits. This isolated output eliminates ground loops, large common mode signals and other types of interference.

Upscale burnout protection is provided as standard. In the event the thermocouple opens, the transmitter output will go offscale high. Option B provides downscale burnout protection (transmitter output grows low).
           
TYPICAL APPLICATIONS

Eliminates ground loops and common mode signals for temperature monitoring, control and data acquisition.

INPUT RANGE
select any type thermocouple (min span 5 mV)

OUTPUT RANGE
Voltage select any range from -10 V to + 15 V,
10 mA max load (min. span 0.2V)
Current select any range from 0 to 50 mA max.,
>24 V compliance (1200 ohms max at 20 mA)
18 V compliance if full scale output > 20 mA

OUTPUT RIPPLE
(Peak-to-Peak) < 0.1% of span

ISOLATION
Output / Input > 500 megohms
Breakdown Voltage > 1000 VAC rms
Breakdown, Power / Circuitry > 1500 VAC rms

ACCURACY
±0.1% of span at endpoints

COMMON MODE REJECTION
120 dB, DC to 60 Hz

OPERATING TEMPERATURE
14°F to 140°F/–10°C to 60°C

TEMPERATURE STABILITY
±(0.02% of span + 1.3 uV)/°C max

POWER
115 VAC ±10%, 50/60 Hz (2.5 W max)
230 VAC ±10%, 50/60 Hz (2.5 W max)
(DC Power Option)
24 VDC (limits 21-32 VDC)
12 VDC (limits 10-16 VDC)

Isolation, DC power supply to input common: 10 megohms

Mighty Module Dimension Drawing

PIN 1
PIN 2
PIN 3
T/C Term +
T/C Term -
PIN 7
PIN 8
Power Supply +
No Connection
Power Supply -
Input +
Input -
Output +
Output -
Specifications    Manual

Solutions Provider for Signal Conditioning and
Process Control Instrumentation