WILKERSON INSTRUMENT CO., INC.

MM4001 RTD Input
Plug-In Mighty Module Transmitter

Wici Logo
Home Button Wilkerson Instrument Co.    800-234-1343 Wilkerson Instrument Co Blog PageWilkerson Instrument Co LinkedIn PageShopping Cart

MM4001

MM4001
RTD Input
Plug-In
Mighty Module
Transmitter

$360.00

The following information must be entered to complete your order:
See "Specifications" below for Input and Output range limits.

Power:

Input:
Zero Scale
Full Scale
Units
  RTD Element Type
Output: Zero Scale
Full Scale
Units
  Isolation

Quantity:

 

Don't Forget Your Accessories
DMP008 8-Pin Socket for Panel or DIN-Rail Mounting $20.00
Quantity:
Specifications
CLP1 Hold Down Assembly $20.00
Quantity:
Specifications
HKB-HK2D-8 Explosion Proof Housing With DMP008 Installed $325.00
Quantity:
Specifications
DR1 DIN-Rail, 35mm Symmetrical, 39 inches (1 meter) $25.00
Quantity:
Specifications
TRK48 PVC Snap-Track, 4 ft, for MP011 $30.00
Quantity:
Specifications
 
  • Features
  • Description
  • Specifications
  • Dimensions
  • Connections
  • Provides DC Output Proportional to an RTD Input
  • 3-Wire or 2-Wire, 10 ohms to 2000 ohms RTDs
  • Unlimited Choice of Input / Output Ranges (Within specified range limits)
  • Linearized for Platinum RTDs
  • Fully Isolated Output Available
  • Choice of Power Options
  • 10 Year Warranty

The MM4001 provides an output voltage or current proportional to an RTD input signal. It is useful in measuring temperatures with a variety of RTDs.

All Wilkerson products are designed with RFI filters and lightning protection to reduce susceptability to electrical noise and damage by lightning.

The module utilizes a single constant current source to excite the RTD. An accurate and stable lead wire compensation circuit uses the third lead of the 3-wire RTD to compensate for the RTD lead resistance.

TYPICAL APPLICATIONS

Temperature control, monitoring, and data acquisition

RTD INPUT
3-Wire or 2-Wire, 10 ohms to 2000 ohms

INPUT RANGE
select any range within RTD limit [min span 25°F/14°C (100°F/55°C with 10 ohms RTD)]

OUTPUT RANGE
Voltage select any range from -10 V to +15 V,
10 mA max load (min span 0.2 V)
Current select any range from 0 to 50 mA max
>24 V compliance (1200 ohms max at 20mA)
18 V compliance for ISO option if full scale output >20 mA

EXCITATION CURRENT

RTD Type Current
10 ohm
100 ohm
1000 ohm
2000 ohm
10 mA
5 mA
0.5 mA
0.2 mA

ISOLATION (Optional)
Output / Input >500 megohms
Breakdown Voltage >1000 VAC rms
Breakdown, Power / Circuitry >1500 VAC rms

OPEN SENSOR OUTPUT
> full scale

ACCURACY
±0.1% of span

LINEARITY
±0.05% of span (Pt RTD, output vs temp)
±0.05% of span, (temp >32°F/0°C)
±0.15% of span, (temp <32°F/0°C)
(others, output vs res) ±0.01% of span

COMMON MODE REJECTION
120 dB, DC to 60 Hz

OUTPUT RIPPLE
(Peak-to-Peak) <0.1% of span

OPERATING TEMPERATURE
14°F to 140°F/–10°C to 60°C

TEMPERATURE STABILITY
±0.02% of span or 0.025°C/°C, whichever is greater

POWER
115 VAC ±10%, 50/60 Hz (2.5 W max)
230 VAC ±10%, 50/60 Hz (2.5 W max)
(DC Power Option)
24 VDC (limits 21-32 VDC)
12 VDC (limits 10-16 VDC)

Isolation, DC power supply to input common: 10 megohms

Mighty Module Dimension Drawing

PIN 1
PIN 2
PIN 3
PIN 4
PIN 5
PIN 6
PIN 7
PIN 8
Power AC L1 or DC +
No Connection
Power AC L2 or DC -
RTD Lead Compensation
RTD -
RTD +
Output +
Output -
Specifications    Manual

Solutions Provider for Signal Conditioning and
Process Control Instrumentation