RTD INPUT
3-Wire or 2-Wire, 10 ohms to 2000 ohms
INPUT RANGE
select any range within RTD limit [min span 25°F/14°C (100°F/55°C with 10 ohms RTD)]
OUTPUT RANGE
Voltage select any range from -10 V to +15 V,
10 mA max load (min span 0.2 V)
Current select any range from 0 to 50 mA max
>24 V compliance (1200 ohms max at 20mA)
18 V compliance for ISO option if full scale output >20 mA
EXCITATION CURRENT
RTD Type |
Current |
10 ohm
100 ohm
1000 ohm
2000 ohm
|
10 mA
5 mA
0.5 mA
0.2 mA
|
ISOLATION (Optional)
Output / Input >500 megohms
Breakdown Voltage >1000 VAC rms
Breakdown, Power / Circuitry >1500 VAC rms
OPEN SENSOR OUTPUT
> full scale |
ACCURACY
±0.1% of span
LINEARITY
±0.05% of span (Pt RTD, output vs temp)
±0.05% of span, (temp >32°F/0°C)
±0.15% of span, (temp <32°F/0°C)
(others, output vs res) ±0.01% of span
COMMON MODE REJECTION
120 dB, DC to 60 Hz
OUTPUT RIPPLE
(Peak-to-Peak) <0.1% of span
OPERATING TEMPERATURE
14°F to 140°F/–10°C to 60°C
TEMPERATURE STABILITY
±0.02% of span or 0.025°C/°C, whichever is greater
POWER
115 VAC ±10%, 50/60 Hz (2.5 W max)
230 VAC ±10%, 50/60 Hz (2.5 W max)
(DC Power Option)
24 VDC (limits 21-32 VDC)
12 VDC (limits 10-16 VDC)
Isolation, DC power supply to input common: 10 megohms |