The MM1600 and MM1610 monitor an AC input signal and trip a dpdt, 5 A relay when the input exceeds the desired level. Normal operation has the relay energized for the non-alarm condition and de-energized for an alarm condition. This provides a “fail-safe” alarm condition for loss of power to the module. The alarm has a set of red/green LEDs to indicate alarm status.
A deadband adjustment allows a deadband of 0.5% to 100% of span to be set into the module. The deadband is symmetrical about the setpoint.
With the latching option, the alarm has no deadband control. Once the limit has been reached the alarm latches and power to the module must be momentarily interrupted to reset the alarm.
All Wilkerson products are designed with RFI filters and lightning protection to reduce susceptability to electrical noise and damage by lightning.
TYPICAL APPLICATIONS
AC motor/current limit, AC power status or demand warning.