The MM1200 monitors any thermocouple input signal and trips a dpdt, 5 A relay when the input exceeds the desired level. Normal operation has the relay energized for the non-alarm condition and de-energized for an alarm condition. This provides a fail-safe alarm condition for loss of power to the module. The alarm has a set of red/ green LEDs to indicate the alarm status.
A deadband adjustment allows a deadband of 0.5% to 100% of span to be set into the module. The deadband is symmetrical about the setpoint.
With the latching option, the alarm has no deadband control. Once the limit has been reached, the alarm latches and power must be momentarily interrupted to reset the alarm.
Cold junction compensation is provided by a solid state temperature sensor embedded in the thermocouple terminal strip.
All Wilkerson products are designed with RFI filters and lightning protection to reduce susceptibility to electrical noise and damage by lightning.
Upscale burnout protection is provided as standard. In the event the thermocouple opens, the module behaves as though the input goes offscale high. Option B provides downscale burnout
protection (module behaves as though the input goes low).
TYPICAL APPLICATIONS
Heater/cooler control, HI/LO temperature alarm.