The MM1005 monitors a DC current input and trips a dpdt, 5 A relay when the input exceeds the desired level. Normal operation has the relay energized for the non-alarm condition and it de-energizes for an alarm condition. This provides a fail-safe alarm condition for loss of power to the module. The alarm has a set of red/ green LEDs to indicate alarm status.
The module contains a 24 VDC transmitter power supply specifically designed for use with two-wire and other 24 VDC powered transmitters.
The deadband adjustment allows a deadband of 0.5% to 100% of span to be set into the module. The deadband is symmetrical about the setpoint.
All Wilkerson products are designed with RFI filters and lightning protection to reduce susceptibility to electrical noise and damage by lightning.
TYPICAL APPLICATIONS
HI/LO pressure alarm, level/position control, temperature alarm, etc.