The MM1000 monitors a DC input signal and trips a dpdt, 5 A relay when the input exceeds the desired level. Normal operation has the relay energized for the non-alarm condition and de-energized for an alarm condition. This provides a fail-safe alarm condition for loss of power to the module. Option R reverses this mode of operation. The alarm has a set of red/green LEDs to indicate alarm status.
The MM1000 deadband adjustment allows a deadband of 0.5% to 100% of span to be set into the module. The deadband is symmetrical about the setpoint.
All Wilkerson products are designed with RFI filters and lightning protection to reduce susceptibility to electrical noise and damage by lightning.
TYPICAL APPLICATIONS
DC Motor/current limit, level/position control, HI/LO pressure alarm, power demand warning.