The FR1020 monitors a DC input signal and provides two sets of SPDT, 5 A alarm relays with two independently adjustable setpoints. Each setpoint has a set of red/green LEDs to indicate alarm status. The configuration of each alarm relay is user-settable as follows:
High or Low - High selects alarm on an increasing signal. Low selects alarm on a decreasing signal.
Normal or Reverse - Normal position selects fail-safe operation (loss of power will result in alarm condition). The relays are energized in the nonalarm condition. When the setpoints are exceeded, the relays de-energize. Selecting the reverse position reverses this logic.
Deadband or Latching – Deadband selects two independently adjustable deadband controls. Deadband for each alarm is adjustable from 0.1% to 100% of the input span. The deadband is symmetrical about the setpoint. With latching selected the alarms will latch when a setpoint is exceeded, and can not be reset unless the input no longer exceeds a setpoint. Reset may be accomplished by remote contact closure or by momentary power interruption. (Several reset inputs may be tied to one reset contact, but note that all negative inputs will be tied together.)
All Wilkerson products are designed with RFI filters and lightning protection to reduce susceptibility to electrical noise and damage by lightning.