WILKERSON INSTRUMENT CO., INC.

DM6010 AC Input DIN-Rail Mounted
Field Rangeable Isolated Output Transmitter

Wici Logo
Home Button Wilkerson Instrument Co.    800-234-1343 Wilkerson Instrument Co Blog PageWilkerson Instrument Co LinkedIn PageShopping Cart

DM6010UR/cUR Logo

DM6010
AC Input
DIN-Rail Mounted
Field Rangeable
Isolated Output Transmitter

$485.00

We will calibrate this field rangeable product to your specifications at no charge.  It can be changed in the field if desired.

The following information must be entered to complete your order:
See "Specifications" below for Input and Output range limits.

Power:

Input:
Zero Scale
Full Scale
Units
Output:

Quantity:

 

Don't Forget Your Accessories
DR1 DIN-Rail, 35mm Symmetrical,
39 inches (1 meter)
$25.00
Quantity:
Specifications
 
  • Features
  • Description
  • Specifications
  • Dimensions
  • Connections
  • Spans from 0.16 V rms to 256 Vrms
  • Selectable Response Time & Filter
  • Plug-In Terminal Blocks
  • Standard DIN-Rail Mount with Easy Snap-On Snap-Off
  • User-Settable Input and Output Ranges
  • Fully Labeled Jumper Positions for Easy Range Settings
  • Connections and Ranging Readily Accessible from the Front
  • Choice of Power Options
  • User Write-On Label
  • Permanent Warranty

The DM6010 provides an isolated voltage or current output proportional to the RMS value of an AC voltage or current input. The true RMS measurement capability allows accurate measurements of distorted sine wave sources as well as complex wave shapes such as a phase angle modulated SCR drive output.

All Wilkerson products are designed with RFI filters and lightning protection to reduce susceptibility to electrical noise and damage by lightning. It utilizes a feedback VCO to develop a pulse train with a duty cycle proportional to the input signal amplitude. This pulse train is coupled through a pulse transformer to the output circuitry, where the duty cycle data is converted to a proportional DC output level.

Connections are made via two 4-pin plug-in terminal blocks. These terminal blocks allow the product to be removed without unwiring the connections.

TYPICAL APPLICATIONS
Useful for measuring and control, accurate AC measurements, and data acquisition.

INPUT
Span
Voltage 0.016 V to 256 V
Current 0.8mA to 100 mA
  (For inputs above 100 mA, use P/N689 0.1 ohm Shunt.)
Frequency 47 Hz to 1000 Hz

SPAN ADJUSTMENT
+5% to -55% of selected range
ZERO ADJUSTMENT

50% elevated

INPUT IMPEDANCE
Voltage 1 megohm
Current 20 ohms

CREST FACTOR
PEAK/RMS + 6.3

OUTPUT

Voltage
0/.25 V
0/1 V
1/5 V
0/5 V
0/10 V
-5/+5 V
-10/+10 V
Current
0/1 mA
0/4 mA
4/20 mA
0/20 mA

OUTPUT LOGIC
Normal or Reverse Acting

DRIVE CAPABILITY
Voltage: 5 mA
Current: >24 Compliance

OUTPUT RIPPLE
(Peak-to-Peak) <0.1% of full scale

ISOLATION
Resistance >500 megohms
Voltage Rating >1000 VAC rms Sinewave

ACCURACY
±0.3% of span

OPERATING TEMPERATURE
14 to 140 °F/-10 to +60 °C

TEMPERATURE STABILITY
±(0.01% of span) /°C

POWER
Standard
115 VAC + 10%, 50/60 Hz
230 VAC + 10%, 50/60 Hz
Optional
115/230 VAC Selectable ±10%, 50/60 Hz
24 VAC + 10%, 50/60 Hz
24 VDC (21 to 32 VDC)
12 VDC (10 to 16 VDC)
Wattage 2.5 W max

DIN Mod Series Dimension Drawing

Terminal 1
Terminal 2
Terminal 3
Terminal 4
Terminal 5
Terminal 6
Terminal 7
Terminal 8
High Range Input
Input Common
Input Common
Low Range Input
Output +
Output -
Power AC L1 or DC +
Power AC L2 or DC -
Specifications    Manual

Solutions Provider for Signal Conditioning and