WILKERSON INSTRUMENT CO., INC.

DM4130 Thermocouple Input DIN-Rail Mounted
Field Rangeable Isolated Output
Linearized Transmitter

Wici Logo
Home Button Wilkerson Instrument Co.    800-234-1343 Wilkerson Instrument Co Blog PageWilkerson Instrument Co LinkedIn PageShopping Cart

DM4130UR/cUR Logo

DM4130
Thermocouple Input
DIN-Rail Mounted
Field Rangeable
Isolated Output
Linearized Transmitter

$455.00

We will calibrate this field rangeable product to your specifications at no charge.  It can be changed in the field if desired.

The following information must be entered to complete your order:
See "Specifications" below for Input and Output range limits.

Power:

Input:
Zero Scale
Full Scale
Units
  Thermocouple Type
Output:

Quantity:

 

Don't Forget Your Accessories
DR1 DIN-Rail, 35mm Symmetrical,
39 inches (1 meter)
$25.00
Quantity:
Specifications
 
  • Features
  • Description
  • Specifications
  • Dimensions
  • Connections
  • Spans from 6.25% to 100% of T/C Range
  • Linearized for J, K, R, S, T, E, and N Thermocouples
  • Provides a Fully Isolated DC Output Proportional to T/C Input
  • Plug-In Output Terminal Block
  • Standard DIN-Rail Mount with Easy Snap-On Snap-Off 
  • Connections and Ranging Readily Accessible from the Front
  • User-Settable Input and Output Ranges
  • Fully Labeled Jumper Positions for Easy Range Settings
  • Choice of Power Options
  • User Write-On Label
  • Permanent Warranty

The DM4130 provides an isolated voltage or current output proportional to temperature as measured with a thermocouple. Any thermocouple may be used, and types J, K, R, S, T, E, and N can be linearized.

A microprocessor controls span and offset settings, performs cold junction compensation calculations, and performs a table look-up for linearization.

All Wilkerson products are designed with RFI filters and lightning protection to reduce susceptibility to electrical noise and damage by lightning. It utilizes a feedback VCO to develop a pulse train with a duty cycle proportional to the input signal amplitude. This pulse train is coupled through a pulse transformer to the output circuitry, where the duty cycle data is converted to a proportional DC output level.

Connections are made via two 4-pin terminal blocks. The lower terminal blocks allow the product to be removed without unwiring the connections.

TYPICAL APPLICATIONS
Useful for temperature monitoring, control and data acquisition.

INPUT
Span Adjustment
Minimum (5 mV input minimum)
Maximum 100% of T/C range
Offset Adjustment 0% to 90% of T/C range

COLD JUNCTION COMPENSATION
± 0.25°C accuracy

IMPEDANCE
1 megohm

UPDATE PERIOD
4/sec

OUTPUT

Voltage
0/.25 V
0/1 V
1/5 V
0/5 V
0/10 V
-5/+5 V
-10/+10 V
Current
0/1 mA
0/4 mA
4/20 mA
0/20 mA

OUTPUT LOGIC
Normal or Reverse Acting

DRIVE CAPABILITY
Voltage 5 mA
Current >24 V Compliance

OUTPUT RIPPLE
(Peak-to-Peak) <0.1% of full scale

ISOLATION
Resistance >500 megohms
Voltage Rating >1000 VAC rms sine wave

ACCURACY
±0.1% of span

LINEARIZATION
+ 0.25°C of NIST tables
full range of J, K, R, S, T, E, N

COMMON MODE REJECTION
>120 dB, DC to 60 Hz

OPERATING TEMPERATURE
14 to 140 °F (-10 to 60 °C)

TEMPERATURE STABILITY
±(0.01% of span)/°C

POWER
Standard
115 VAC + 10%, 50/60 Hz
230 VAC + 10%, 50/60 Hz
Optional
115/230 VAC Selectable ±10%, 50/60 Hz
24 VAC + 10%, 50/60 Hz
24 VDC (21 to 32 VDC)

DIN Mod Series Dimension Drawing

Terminal 1
Terminal 2
Terminal 3
Terminal 4
Terminal 5
Terminal 6
Terminal 7
Terminal 8
Shield
T/C Input +
No Connection
T/C Input -
Output +
Output -
Power AC L1 or DC +
Power AC L2 or DC -
Specifications    Manual

Solutions Provider for Signal Conditioning and
Process Control Instrumentation