WILKERSON INSTRUMENT CO., INC.

DM4003 Potentiometer Position Input
DIN-Rail Mounted Field Rangeable
Isolated Output Transmitter

Wici Logo
Home Button Wilkerson Instrument Co.    800-234-1343 Wilkerson Instrument Co Blog PageWilkerson Instrument Co LinkedIn PageShopping Cart

DM4003UR/cUR Logo

DM4003
Potentiometer Position Input
DIN-Rail Mounted
Field Rangeable
Isolated Output Transmitter

$410.00

We will calibrate this field rangeable product to your specifications at no charge.  It can be changed in the field if desired.

The following information must be entered to complete your order:
See "Specifications" below for Input and Output range limits.

Power:

Input: Zero Scale
Full Scale
Units
  Total Potentiometer Resistance
Ohms
Output:

Quantity:

 

Don't Forget Your Accessories
DR1 DIN-Rail, 35mm Symmetrical,
39 inches (1 meter)
$25.00
Quantity:
Specifications
 
  • Features
  • Description
  • Specifications
  • Dimensions
  • Connections
  • 100 ohm to 100 kilohm Potentiometer
  • Selectable Response Time/Filter
  • Provides a Fully Isolated DC Output Proportional to Wiper Position
  • User Write-On Label
  • User-Settable Input and Output Ranges
  • Fully Labeled Jumper Positions for Easy Range Settings
  • Plug-In Terminal Blocks
  • Standard DIN-Rail Mount with Easy Snap-On Snap-Off
  • Connections and Ranging Readily Accessible from the Front
  • Choice of Power Options
  • Permanent Warranty

The DM4003 provides an isolated voltage or current output proportional to the position of a potentiometer wiper. The output is fully isolated from input, line power and ground. The unit is useful in eliminating ground loops and common mode signals.

Input and output ranges are user settable. The output response may be normal or reverse-acting. A fully-labeled set of jumpers selects the input and output ranges.

All Wilkerson products are designed with RFI filters and lightning protection to reduce susceptibility to electrical noise and damage by lightning. It utilizes a feedback VCO to develop a pulse train with a duty cycle proportional to the input signal amplitude. This pulse train is coupled through a pulse transformer to the output circuitry, where the duty cycle data is converted to a proportional DC output level.

Connections are made via two 4-pin plug-in terminal blocks. These terminal blocks allow the product to be removed without unwiring the connections.

TYPICAL APPLICATIONS
A useful interface for monitoring valve and actuator position, or for generating test signals.

INPUT
Input Potentiometer Value 100 ohm to 100 kilohm
Excitation 1 VDC
Span Selections for Full Scale Output (% rotation)
25%, 50%, 75% & 100%
Offset ±0% to 100% of span

OUTPUT

Voltage
0/.25 V
0/1 V
1/5 V
0/5 V
0/10 V
-5/+5 V
-10/+10 V
Current
0/1 mA
0/4 mA
4/20 mA
0/20 mA

OUTPUT LOGIC
Normal or Reverse Acting

DRIVE CAPABILITY
Voltage 5 mA
Current >24 V compliance

OUTPUT RIPPLE
(Peak-to-Peak) <0.1% of full scale

ISOLATION
Resistance >500 megohms
Voltage Rating >1000 VAC sinewave

RESPONSE TIME (99%)
2, 20, 50, 500 milliseconds

ACCURACY
±0.1% of span

LINEARITY
±0.1% of span

COMMON MODE REJECTION
>100 dB, DC to 60 Hz

OPERATING TEMPERATURE
14 to 140 °F/-10 to 60 °C

TEMPERATURE STABILITY
±0.01% of span/°C

POWER
Standard
115 VAC + 10%, 50/60 Hz
230 VAC + 10%, 50/60 Hz
Optional
115/230 VAC Selectable ±10%, 50/60 Hz
24 VAC + 10%, 50/60 Hz
24 VDC (21 to 32 VDC)
12 VDC (10 to 16 VDC)
Wattage 2.5 W max

DIN Mod Series Dimension Drawing

Terminal 1
Terminal 2
Terminal 3
Terminal 4
Terminal 5
Terminal 6
Terminal 7
Terminal 8
Input FS
Input Wiper
Input Zero
Shield
Output +
Output -
Power AC L1 or DC +
Power AC L2 or DC -
Specifications    Manual

Solutions Provider for Signal Conditioning and