TSP10
Pipefitting
Surge Protectors
FEATURES
 |
10kA surge
current capacity |
 |
Compact
design |
 |
Machined
316 stainless steel housing |
 |
½"
NPT Thread |
 |
Automatic
Reset |
 |
Can be
mounted in hazardous areas |
 |
NEMA 4X
rated housing |
 |
Pre-wired
leads |
 |
Conduit
Mounted |
DESCRIPTION
Citel's
new TSP10 surge protection barrier is designed to limit transients to critical
process transmitters. Principal use is on 4-20 mA
current loops, signal lines and low speed data
lines feeding transducers, flow meters, water level
monitors, control circuits and variety of similar field sensor,
signal and OEM applications. It can also be used
for intrinsic safety and explosion-proof applications.
The units mounts in an available conduit or cable
gland opening found on most process transmitters.
SPECIFICATIONS
| Unprotected
Field Circuit |
Red,
green/yellow, black wires |
| Operating
voltage |
<48
V |
| Leakage
current |
<5 µA |
| Protected
Circuit |
Red,
green/yellow, black wires |
| Differential
mode |
<85
V |
| Common
mode |
500 V |
| Entity
Parameters |
|
| CSA
control drawing no. |
116-0187 |
| Voltage Vo |
<48
V |
| Current Io |
<250
mA |
| Power Po |
<1.3
W |
| Internal
capacitance (Ca) |
<1.5
nF |
| Internal
inductance (La) |
<200 µH |
| Nominal
Discharge Current |
10 kA
(8/20 µs)
per lead |
| Nominal
Response Time |
|
| Symmetric |
1 ns |
| Asymmetric |
100 ns |
| Bandwidth |
>40
kHz |
| Mechanical |
|
| Mounting
Type |
1/2"
NPT |
| Dimensions
(mm) |
75 x 22 |
| Weight
175 g |
(6.3
oz.) |
| Terminal
Connection |
Three
-16 AWG flying leads
|
| Rating |
Intrinsic
safety, explosion-proof; Type 4X |
| Ambient Temperature
|
|
| Safe area application
|
-30° C to
+80° C
(-22° F to
+176° F)
|
| Hazardous area application
|
-30° C to
+80° C
(-22° F to
+176° F)
|
WIRING