Wilkerson Instrument Co. Homepage A World of Signal Conditioning & Process Control Instrumentation Products


DL Series
One Pair - DIN Rail Mountable
Surge Protectors

FEATURES

bullet

Ultra fast response time

bullet

Multiple stage circuitry

bullet

Resets Automatically

bullet

Can be easily mounted on a DIN Rail DR1

bullet

Plug- in module

DESCRIPTION

Citel DL Series has been designed to protect telephone and data lines against lightning surges and electrical transients. Its large power handling and fast response time will protect your sensitive equipment against the worst lightning surges.

It uses state of the art multi-stage circuitry which consists of heavy duty three element gas tubes and solid state diodes that automatically reset after every electrical surge.  Under the most severe conditions, the Citel DL Series will fail short leaving your equipment fully protected.

SPECIFICATIONS

Model: DL170 DL48 DL24 DL12 DL06
Application: Telephone
Lines
Leased
Lines
4 - 20mA
Loop Lines
Telemetry
Load Cells
RS485, RS422
RTD's, THC's
Series Resistance: 4.7 Ohm 4.7 Ohm 4.7 Ohm 4.7 Ohm 4.7 Ohm
Capacitance: 70 pF 200 pF 300 pF 400 pF 900 pF
Maximum Line Current: 200 mA 200 mA 200 mA 200 mA 200 mA
Maximum Line Voltage: 170 V 48 V 24 V 12 V 6 V
Clamping Voltage: 190 V 60 V 30 V 20 V 12 V
Power Handling:
(8/20us- 10 x's)
(8/20us- 1 x 's)

10 kA
20 kA

10 kA
20 kA

10 kA
20 kA

10 kA
20 kA

10 kA
20 kA
End of Life Characteristics:
(U=220/Veff/Icc>10A)
Short
Circuit
Short
Circuit
Short
Circuit
Short
Circuit
Short
Circuit
 

Mechanical Diagram
All dimensions are in mm.

Mounting: DIN Rail - DR1
I/O Connections: Screw terminals
Operating Temperature: -40 to 85 C

Electrical Diagram

 

Gt: Three Element Gas Tube
D: Clamping Diode