DM4380AUR/cUR Logo

DM4380A
DC Input
DIN-Rail Mounted
Field Rangeable
Isolated Output Transmitter

$425.00

We will calibrate this field rangeable product to your specifications at no charge.  It can be changed in the field if desired.

The following information must be entered to complete your order:
See "Specifications" below for Input and Output range limits.

Power:

Input:
Zero Scale
Full Scale
Units
Output:

Quantity:

 

Don't Forget Your Accessories
DR1 DIN-Rail, 35mm Symmetrical,
39 inches (1 meter)
$25.00
Quantity:
Specifications
 
  • Features
  • Description
  • Specifications
  • Dimensions
  • Connections
  • Allows Inputs to ±256 V or ±100 mA
  • 15 mV or 0.8 mA Minimum Full Scale Input
  • Provides a Fully Isolated DC Output Proportional to DC Input
  • Plug-In Terminal Blocks
  • Standard DIN-Rail Mount with Easy Snap-On Snap-Off
  • User-Settable Input and Output Ranges
  • Fully Labeled Jumper Positions for Easy Range Settings
  • Connections and Ranging Readily Accessible from the Front
  • Choice of Power Options
  • User Write-On Label
  • Permanent Warranty

The DM4380A provides a DC output proportional to a DC input. The output is fully isolated from input, line power and ground. The unit is useful in eliminating ground loops and common mode signals.

Input and output ranges are user-settable. Each may be voltage or current, with or without offset. The output response may be normal or reverse-acting. A fully labeled set of jumpers selects the input and output ranges.

All Wilkerson products are designed with RFI filters and lightning protection to reduce  susceptibility to electrical noise and damage by lightning. It utilizes a feedback VCO to develop a pulse train with a duty cycle proportional to the input signal amplitude. This pulse train is coupled through a pulse transformer to the output circuitry, where the duty cycle data is converted to a proportional DC output level.

Connections are made via two 4-pin plug-in terminal blocks. These terminal blocks allow the product to be removed without unwiring the connections.

TYPICAL APPLICATIONS
Eliminates ground loops and common mode signals. Use for voltage/current scaling and conversion with isolation for buffering and noise reduction. Single unit replacement module provides field rangeability for all normal input and output ranges.

INPUT RANGE
Limits (User-Settable)
select any voltage between -256 and +256 VDC
select any current between -100 and +100 mADC

Span
Voltage - any voltage span from 15 mV to 256 V
Current - any current span from 0.8 mA to 100 mA

INPUT OFFSET
± 0, 25, 75, 100% Full Scale.

INPUT IMPEDANCE
Voltage - 1 megohm
Current - 20 ohms

OUTPUT
Voltage
0/.25 V
0/1 V
1/5 V
0/5 V
0/10 V
-5/+5 V
-10/+10 V
Current
0/1 mA
0/4 mA
4/20 mA
0/20 mA

OUTPUT LOAD
Voltage 10 mA max. (1 kilohm at 10 V)
Current > 24 V compliance (1200 ohms max. at 20 mA)

OUTPUT RESPONSE
(User Settable) normal or reverse–acting (example 10 to 0 VDC)

OUTPUT RIPPLE
(Peak–to–Peak) < 0.1% of span

ISOLATION
Output / Input > 500 megohms
Breakdown, Output / Input > 1000 VAC rms Sinewave
Breakdown, Power / Circuitry > 1500 VAC rms Sinewave

RESPONSE TIME
(Range Dependent) < 100 ms

ACCURACY
±0.1% of span (exclusive of user–supplied calibration instruments)

LINEARITY
±0.05% of span

COMMON MODE REJECTION
120 dB, DC to 60 Hz

OPERATING TEMPERATURE
14°F to 140°F /-25/75°C

TEMPERATURE STABILITY
±(0.02% of span + 2 μV)/°C max

POWER
Standard
115 VAC + 10%, 50/60 Hz
230 VAC + 10%, 50/60 Hz

Optional
115/230 VAC Selectable ±10%, 50/60 Hz
24 VAC + 10%, 50/60 Hz
24 VDC (21 to 32 VDC)
12 VDC (10 to 16 VDC)
Wattage 2.5 W max

DIN Mod Series Dimension Drawing

Terminal 1
Terminal 2
Terminal 3
Terminal 4
Terminal 5
Terminal 6
Terminal 7
Terminal 8
Input +
Input -
Shield
No Connection
Output +
Output -
Power AC L1 or DC +
Power AC L2 or DC -
Specifications    Manual