RTD Two Wire Transmitters and how they work

RTD 2 Wire Transmitters and how they work

An RTD (Resistance Temperature Detector) is a metal which changes its electrical resistance when its temperature changes.

The most common metal used for precision resistance measurements is platinum. Platinum is chosen because it is a noble metal which is stable, corrosion resistant, does not oxidize readily, and is easily workable into thin wire.

Copper is also used as an RTD. Because of its low resistance value, RTD’s of copper are low in ohms value and requires accurate measurements of the resistance when used as an RTD.

Because copper wire changes resistance with temperature and it is used to connect the RTD to the Transmitter, lead length between the RTD and the 2W Transmitter must be taken into consideration.

RTD SENSOR

Three versions of RTD’s compensate for lead length between the RTD and the Transmitter.

The signal from the RTD is typically developed by having a constant current flow through the RTD and the voltage across the RTD is measured to determine the resistance of the RTD.

Resistance = Voltage/Current.

RTD Wiring Diagram

2 WIRE – Current flows through the RTD. The signal is the voltage drop across the RTD. The Cu leads must be short enough so their resistance change does not create a serious error in the measurement.

3 WIRE – Same as the 2 Wire except a Cu lead is brought from the RTD bottom to the TX. It allows the voltage dropped by the Common Cu lead to be measured. This voltage is doubled and subtracted from the signal voltage. This negates the voltage drop in the Common and Current Cu leads.

4 WIRE – The signal Cu leads go directly to the RTD. They allow the voltage across the RTD to be measured without the Current and Common Cu leads having any effect. This is the desired RTD setup for the most accurate measurement, when Cu leads could be a problem due to their length.

The transmitter has to be well designed so it does not have its current source, which excites the RTD, drift with ambient temperature changes. The circuits which process the signals must also be stable.

RTD’s are not perfectly linear with resistance vs temperature. Platinum RTD’s can be compensated. If the Transmitter is an analog design, linearization is accomplished by feeding a small amount of the RTD signal back to the current source which excites the RTD. This feedback increases the current a little for every positive change in temperature. With proper compensation very high accuracy can be obtained.

Microprocessor based Transmitters can manage Cu leads in a similar fashion to the analog version, but the add/subtract math is done by the microprocessor.

Linearization can be done more accurately with a microprocessor utilizing a lookup table of values.

©  Joe E. Wilkerson  2012

 

 

Automatic Temperature Control In a Sugar Refinery

AUTOMATIC TEMPERATURE CONTROL IN A SUGAR REFINERY

TW303 LOW-COST RTD TWO-WIRE TRANSMITTER

TW303 Two-Wire Transmitter

TW303 - Specifications and I/O manual

FEATURES:

  • Provides 4/20 mAdc current output  proportional to an RTD input
  • Any 2-wire or 3-wire RTD  (100 ohms to 2000 ohms)
  • Linearized for platinum RTD
  • Any input range within RTD limit  (50°F minimum span)
  • Low-drift chopper-stabilized input
  • Operating temperature range -13°F to 176°F
  • Temperature stability of ±0.02% of span per °C
  • Operates on 12 V to 48 VDC
  • Conformal coated to resist corrosion,  moisture and fungus
  • Low cost
  • Small size – 50mm X 50mm
  • Our standard 5 year warranty

PROBLEM:                              Specification Sheet PDF      I/O Manual PDF

To replace manually read thermometers with 3-wire, 100 ohm, platinum RTDs allowing all temperature readings to be taken in a central control room. Also, to provide automatic temperature control for more efficient control of the refining process.

INTRODUCTION:

Historically, sugar refineries are reluctant to spend money on capital equipment. As a result, they tend to be slow in automating their process. Many still utilize manual thermometers that require some-one to “make the rounds” to read the temperatures and make manual adjustments to the steam valves.

This process is cumbersome and slow, particularly when trying to maintain constant temperature at multiple sites. Those refineries who have made the plunge have found that automation of the process has among other things, greatly improved the efficiency of the process.

In this particular application, shown in the flow chart, the customer must read and maintain temperatures at multiple locations including in/out temperatures of heat exchangers as well as the top/bottom temperatures in the pan. The pan temperatures must be exactly right in order to “seed” them to make crystal.

 

Steam Flow Chart - Temperature Control In a Sugar Refinery - TW303 - Wilkerson Instrument

Flow Chart

The customer chose to automate the plant with Moore 352E programmable loop controllers to control each temperature control loop, Fisher Controls steam valves and a central computer to poll each controller for CRT readout and data gathering in the control room.

Each Moore 352E can handle up to 5 analog inputs and 3 analog outputs. In addition, the 352E has a resident 24 V power supply capable of powering up to at least 3 current loops. However, in order to read an RTD directly, the 352E must be equipped with an optional RTD input at a cost of about $300 each. By using a low cost 2-wire transmitter, the customer can save ap-proximately $200 per RTD input.

SOLUTION:

The product chosen was the TW303 RTD input 2-wire transmitter. Its small size, low cost, reliability, and versatility in mounting (field or panel mount in a variety of industrial housings and enclosures) made it the ideal choice. The transmitter accepts any 2-wire or 3-wire RTD input and has a minimum span of 50°F. It can be calibrated to cover any range desired within the limits of the RTD selected. The module operates over a temperature range from -13°F to 176°F while providing a temperature stability of ±0.02% of span. It will also operate over a supply voltage range of 12 to 48 VDC.

The transmitter design provides accurate trouble-free operation. A single constant current source excites the RTD, but the low excitation current causes no appreciable self-heating in the RTD. An accurate and stable leadwire compensation circuit uses the third lead of the 3-wire RTD to compensate for the RTD lead resistance. Platinum RTD inputs are linearized and use of low-drift chopper-stabilized amplifiers and special filtering reduces susceptibility to transients and noisy operations. In addition, the electronic board and components are conformal coated to resist corrosion, moisture and fungus associated with harsh industrial environments.

These features, a generous 5 year warranty, customer service second to none in the industry, low cost and a recommendation from the Wilkerson representative, led the customer to choose the TW303.

The customer connected them as shown in the wiring diagram.

Wiring Diagram - Temperature Control In a Sugar Refinery - TW303 - Wilkerson Instrument

Wiring Diagram

COST SAVINGS:

Approximately $200 per RTD input.

**********

Copyright Wilkerson Instrument Company Inc. – USA – 2012

http://www.wici.com

http://www.wici.com/blogs/2012/02/automatic-temperature-control-in-a-sugar-refinery/

 